What is meant by Ferranti Effect?

Published in Electrical Engineering 3 mins read

The Ferranti effect refers to the phenomenon where the voltage at the receiving end of a long AC transmission line is higher than the voltage at the sending end, especially under lightly loaded or no-load conditions.

Understanding the Ferranti Effect

This counter-intuitive voltage rise isn't a simple voltage drop issue. It primarily occurs due to the capacitive charging current in the transmission line. Let's break down the key factors:

  • Line Capacitance: Long transmission lines possess significant capacitance distributed along their length. This capacitance arises from the electric field between the conductors and the ground.
  • Charging Current: Even when no load is connected, the voltage at the sending end charges this capacitance, resulting in a charging current flowing through the line.
  • Voltage Drop (or Rise): This charging current flows through the inductance of the line. The voltage drop across this inductance is in phase with the sending-end voltage. This in-phase relationship, combined with the line's capacitance, causes the voltage at the receiving end to increase above the sending-end voltage.

Essentially, the line behaves like a large capacitor under lightly loaded conditions.

Conditions Favoring the Ferranti Effect

  • Long Transmission Lines: The effect is more pronounced in long lines (typically exceeding 200 km or 125 miles) due to the increased capacitance and inductance.
  • Lightly Loaded or No-Load Conditions: The effect is most noticeable when there's little or no load connected at the receiving end. When there's a substantial load, the inductive voltage drop due to the load current counteracts the capacitive voltage rise.
  • High Voltage Levels: Higher voltage transmission lines have greater charging currents, exacerbating the Ferranti effect.

Implications of the Ferranti Effect

  • Insulation Stress: The increased voltage at the receiving end can overstress the insulation of equipment (transformers, switchgear) connected to the line, potentially leading to damage or failure.
  • Voltage Regulation Issues: The Ferranti effect makes voltage regulation more challenging, requiring careful planning and implementation of voltage control measures.
  • System Protection Challenges: Unexpected voltage rises can complicate the operation of protective relays and other system protection devices.

Mitigation Techniques

Several methods are employed to mitigate the Ferranti effect:

  • Shunt Reactors: Shunt reactors are inductive devices connected in parallel with the transmission line. They absorb the capacitive charging current, thereby reducing the voltage rise.
  • Line Compensation: Series capacitors can be used to compensate for the inductive reactance of the line, reducing the overall impedance and minimizing the voltage rise.
  • Load Management: Maintaining a reasonable load on the line helps to counteract the Ferranti effect.
  • Voltage Regulators: Automatic voltage regulators (AVRs) at substations can help maintain voltage within acceptable limits.

Example

Imagine a very long, unloaded transmission line. The sending end maintains a voltage of 220 kV. Due to the Ferranti effect, the receiving end might experience a voltage as high as 230 kV or more. This increase, though seemingly small, can be detrimental to connected equipment.