How Does an RCBO Work?

Published in Electrical Safety 3 mins read

An RCBO (Residual Current Operated Circuit Breaker with Overcurrent protection) works by constantly monitoring the current flowing through and returning from a circuit and tripping if an imbalance indicating a leakage current is detected, while also providing overcurrent and short-circuit protection like a regular circuit breaker.

Here's a breakdown of its operation:

1. Residual Current (Leakage) Detection:

  • Current Monitoring: The RCBO monitors the current flowing through the live (hot) and neutral conductors of the circuit. Under normal conditions, the current flowing to the load should be equal to the current flowing back from the load.
  • Differential Transformer: A differential transformer (also known as a current transformer) is the heart of the residual current detection mechanism. The live and neutral wires pass through this transformer.
  • Zero Sum: If the currents are equal, the magnetic fields created by the live and neutral conductors within the differential transformer cancel each other out. The resultant magnetic flux is zero, and no current is induced in the secondary winding of the transformer.
  • Leakage Detection: If a fault occurs, such as a short circuit to ground (earth), some of the current will leak away to earth. This creates an imbalance between the live and neutral currents. This difference in current (the residual current) creates a magnetic field in the differential transformer.
  • Tripping Mechanism Activation: The magnetic field induces a current in the secondary winding of the transformer. This current activates a sensitive electronic circuit that trips the circuit breaker. RCBOs are typically designed to trip very quickly, usually within milliseconds, to prevent electric shock. Common tripping thresholds are 10mA, 30mA, 100mA, or 300mA.

2. Overcurrent and Short-Circuit Protection:

  • Thermal Overload Protection: RCBOs include a thermal element, often a bimetallic strip. If the current exceeds the rated current for an extended period (an overload), the bimetallic strip heats up, bends, and trips the breaker. This protects against damage from prolonged overcurrents, such as overloading a circuit with too many appliances.
  • Magnetic Short-Circuit Protection: RCBOs also have a magnetic element, typically a solenoid. In the event of a short circuit, a very large current flows almost instantaneously. This large current energizes the solenoid, which quickly trips the breaker. This protects against the damaging effects of short circuits, such as fire.

3. Combining the Functions:

The RCBO integrates both the residual current protection and the overcurrent/short-circuit protection into a single device. This saves space in the electrical panel and provides comprehensive protection.

Table Summarizing RCBO Protection:

Protection Type Cause Detection Method Action
Residual Current (Earth Leakage) Current leakage to earth Differential Transformer measuring imbalance Trips the breaker
Overcurrent (Overload) Exceeding rated current for a time Bimetallic strip heating and bending Trips the breaker
Short Circuit Direct, low-resistance path Solenoid activation by high current Trips the breaker

In essence, an RCBO is a safety device that protects against electric shock by detecting earth leakage and also protects against overloads and short circuits that can cause fires or damage to equipment.