Adjusting a central heating bypass valve involves fine-tuning it to ensure proper system pressure and prevent pump cavitation when thermostatic radiator valves (TRVs) close. Here's a step-by-step guide based on available information:
-
Heat the system to full capacity: Ensure all radiators are calling for heat (TRVs are open).
-
Locate the bypass valve: This is typically located near the pump or boiler. It will have an adjustment knob, often indicating pressure settings (e.g., 0.1 to 0.5 bar).
-
Initial adjustment: While the system is heating at full capacity, gradually turn the adjustment knob of the bypass valve towards the lowest setting (e.g., 0.1 bar). The goal is to minimize bypass flow unless absolutely necessary.
-
Monitor the bypass pipe: Gradually turn the adjustment knob of the bypass valve towards 0.1 bar until you begin to feel the outlet pipe from the bypass valve begin to feel warm. This warmth indicates that water is flowing through the bypass.
-
Fine-tuning: Once the outlet pipe from the bypass valve begins to feel warm, turn the setting back towards 0.5 bar by half a turn to prevent constant flow. This slight increase ensures the valve isn't always open, only opening when needed to relieve pressure.
-
Check for pump cavitation: Listen to the pump. If it's making excessive noise (gurgling or rattling), it might be cavitating. This can happen when all TRVs close, and there's nowhere for the water to go. If you hear cavitation, slightly increase the bypass valve setting until the noise stops.
- Solution: Increase the bypass valve setting in small increments until the pump noise disappears.
-
Final Adjustment and Optimisation: The optimal setting of your bypass valve may depend on the pressure in your system. You may need to experiment with it by closing all of the TRVs in your house and adjusting the bypass valve until your boiler runs smoothly and your pump doesn't cavitate when all of the TRVs are closed.
Here's a summary of the adjustment procedure in a table:
Step | Action | Purpose |
---|---|---|
1 | Heat the system fully. | Ensure realistic operating conditions. |
2 | Gradually turn the bypass valve towards a lower setting (e.g., 0.1 bar). | Reduce bypass flow. |
3 | Monitor bypass pipe temperature. | Identify when the valve starts to open. |
4 | Turn the setting back up half a turn from when the pipe got warm | Prevent continuous bypass flow |
5 | Check for pump cavitation (noise). | Identify potential issues when TRVs close. |
6 | Adjust bypass valve until pump cavitation disappears. | Ensure adequate flow and protect the pump. |
7 | Re-adjust when all TRVs are closed if necessary | Fine tune the bypass valve to ensure system pressure is adequately stable even when all TRVs are switched off. |
Important Considerations:
- This guide provides a general approach. Always consult your boiler and bypass valve manufacturer's instructions for specific recommendations.
- If you're not comfortable working with your central heating system, it's best to consult a qualified heating engineer.