How to Take an Oil Sample from a Transformer?

Published in Transformer Oil Sampling 4 mins read

Taking an oil sample from a transformer is a crucial maintenance task to assess the dielectric strength and dissolved gases in the oil, indicating the transformer's health.

To take an oil sample from a transformer, you typically access a dedicated sample port, clean the area, connect a sterile syringe or sampling device, extract the required amount of oil carefully, and then properly seal and label the sample for laboratory analysis.

Why Sample Transformer Oil?

Transformer oil serves multiple functions: insulation, cooling, and arc quenching. Regular sampling and analysis, particularly Dissolved Gas Analysis (DGA), can detect internal faults early, preventing costly failures and downtime. Key parameters analyzed include:

  • Dissolved Gases: Indicate decomposition of insulation or oil due to thermal or electrical stress.
  • Moisture Content: Reduces dielectric strength and accelerates insulation aging.
  • Dielectric Strength: Measures the oil's ability to withstand electrical stress.
  • Acidity: Indicates oil degradation and can damage insulation and metallic parts.
  • Particle Count: Shows contamination which can affect dielectric strength and cooling.

Step-by-Step Guide to Sampling

Taking a clean, representative oil sample is critical for accurate analysis. Follow these steps:

1. Preparation & Safety

  • Safety First: Ensure the transformer is de-energized if company policy requires or if working on lower voltage equipment. For critical high-voltage units requiring hot sampling (sampling while energized), follow strict safety protocols, including proper PPE (gloves, safety glasses, arc flash gear if required) and procedures.
  • Gather Equipment:
    • Sterile sampling syringes (typically 50-100 ml) or sample bottles.
    • Clean rags or wipes.
    • Appropriate tools (wrench for sample port cap).
    • Cleaning solution (e.g., isopropyl alcohol).
    • Sample labels.
    • Shipping container/packaging.
  • Locate Sample Port: Transformers usually have designated sample ports, often near the bottom for general samples and sometimes higher up for specific analysis like DGA if a dedicated port exists.

2. Taking the Sample

  • Clean the Area: Thoroughly clean the area around the sample port to prevent contamination.
  • Flush the Port: Slightly open the valve or port to let a small amount of oil drain and flush out any debris or stagnant oil in the pipework. Close it off again.
  • Connect Sampling Device: Connect the sterile syringe or sampling device to the port. Ensure a tight, leak-free connection.
  • Extract the Sample: Open the valve and carefully draw the required amount of oil into the syringe or fill the sample bottle. Fill syringes slowly to avoid drawing in air bubbles, especially crucial for DGA samples.
  • Position the Syringe: As highlighted in the reference, position the syringe correctly during extraction to ensure proper filling and minimize air ingress.
  • Seal the Sample: Once filled, close the valve, disconnect the syringe/device, and immediately cap or seal the sample container securely. For syringes, ensure the valve is closed and cap the end.

3. Post-Sampling

  • Reattach Sample Port Cap: The sample port cap is reattached securely to prevent leaks and contamination.
  • Clean Up: The syringe is wiped clean of oil externally. Clean up any spilled oil around the sample port.
  • Labeling: Label the sample immediately and accurately. Include details like:
    • Transformer ID
    • Sampling Date and Time
    • Location/Site
    • Sample Point (e.g., Bottom Sample Port)
    • Sampler's Name
    • Any relevant operational status (e.g., energized/de-energized, load level).
  • Packing for Shipment: Position the syringe ... and packed for shipment to the laboratory for analysis. Pack the sample container (syringe or bottle) carefully according to laboratory instructions, ensuring it is protected and cannot leak during transit. Use appropriate packaging materials.

Best Practices

  • Always follow the specific procedures provided by the transformer manufacturer and the oil testing laboratory.
  • Use only clean, sterile sampling equipment. Contamination is the most common reason for inaccurate results.
  • Avoid sampling during rain or high humidity conditions if the sample port is exposed, as moisture can enter.
  • Ensure adequate sample volume as required by the testing laboratory for the specific tests requested.
  • Document the sampling process, including any unusual observations.

By following these steps and best practices, you can obtain reliable transformer oil samples for accurate assessment of the unit's condition.